SK 200E Manual for frequency inverters

166

Subject to technical alterations

BU 0200 GB-4411

Method 1
With a normal addressing device (equipped with
an M12 plug for connection to the AS-i bus) the
AS-i can be integrated into the AS-i network via
a suitable access point. The prerequisite for this
is that the AS-i master can be switched off.










Method 2
With an addressing unit (equipped with an M12
plug for connection to the AS-i bus and an
additional M12 plug for an external power
supply), the addressing unit can be directly
connected into the AS-i cable.

NOTE

With the versions SK 220E and SK 230E a battery-operated addressing device is
sufficient.

5.4.5

Technical data for AS interface

Name

Value

SK 220E / SK230E

SK 225E / SK235E

Supply via AS interface connection,
PWR connection (yellow cable)

24V,

max. 25mA

26.5

– 31.6V,

max. 290mA

Slave profile

S-7.A

S -7.0

I/O-Code

7

7

ID Code

A

0

External ID Code 1 / 2

7

F

Address

1A

– 31A and 1B - 31B

(condition as delivered: 0A)

1

– 31

(condition as delivered: 0)

AS-I addressing unit

AS-i

MASTER

AS-i

Power

AS-i addressing unit