6.1.8

Information (Frequency inverter)

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P700

[-01]

...

[-03]

Present operating status

(Present operating status)

0.0 ... 21.4

Display of current messages for the actual operating status of the frequency inverter such as
errors, wanings or the cause of a switch-on block. For details of messages see Section 7

[-01] = Current fault, shows the currently active (unacknowledged) error (Section 7.2.1)

[-02] = Actual warning, shows any current warning message (Section 7.3)

[-03] = Reason FI blocked, shows the reason for a currently active switch-on block

(Section 7.4)

Note

SimpleBox:Only warning messages and errors can be displayed with the Simplebox. Display of
the messages is encoded. For the description of the codes (warning/error numbers), please
refer to the tables in Sections 7.2.1 and 7.3.

ParameterBox: the ParameterBox displays the messages in plain text. The reason for any
switch-on block can also be displayed.

Bus: The display of error messages at bus level is in decimal integer format. If the value is
divided by 10, the display corresponds to the description in Section 7.2.

Example: Display: 20 → Error number: 2.0

P701

[-01]

...

[-05]

Last fault

(Last fault 1 ... 5)

0.0 ... 21.4

This parameter stores the last 5 faults. (Details Section 7)

With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.

P702

[-01]

...

[-05]

Freq. last error

(Last frequency fault 1 ... 5)

S

-400.0 ... 400.0 Hz

This parameter stores the output frequency that was being delivered at the time the fault
occurred. The values of the last 5 errors are stored.

With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.

P703

[-01]

...

[-05]

Current. last error

(Last current fault 1 … 5)

S

0.0 ... 999.9 A

This parameter stores the output current that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.

With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.

P704

[-01]

...

[-05]

Volt. last error

(Last voltage fault 1 ... 5)

S

0 ... 600 V AC

This parameter stores the output voltage that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.

With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.