3 commissioning examples, 1 sk 2x0e - minimal configuration, 2 sk 2x5e - minimal configuration – NORD Drivesystems BU0200 User Manual

Page 156: Commissioning examples

Advertising
background image

5 Commissioning

BU 0200 GB-4411

Subject to technical alterations

155

5.2.3

Commissioning examples

All SK 2xxE models can be operated as delivered.

Standard motor data for a 4-pole standard asynchronous motor of the same power is parameterised.

The PTC input must be bypassed, if a motor with PTC is not available.

Parameter (P428) must be changed if an automatic startup with "Mains On" is required.

5.2.3.1

SK 2x0E - Minimal Configuration

The frequency inverter provides all the necessary low voltages (24VDC / 10V DC).

Function

Setting

Setpoint

External 10kOhm potentiometer

Controller
enable

External switch S1

5.2.3.2

SK 2x5E - Minimal Configuration

Minimal configuration without options

The frequency inverter must be provided with a 24V control voltage.

Function

Setting

Setpoint

Integrated potentiometer P1

Frequency ramp

Integrated potentiometer P2

Controller enable

External switch S1





Frequency inverter
SK 2x5E-...

C

ontrol

term

ina

l bar

44
40

.
.

21
22

.

38
39

L1 - L2/N - L3

115/230/400V

24V=

GND

1/3~ 115/230/400V + PE



Switch S1



Motor PTC





Frequency inverter
SK 2x0E-...

Co

ntro

l terminal b

ar

12*

14**

11

.

43

.

21
22

.

38
39

L1 - L2/N - L3

230/400V

1/3~ 230/400V + PE



Switch S1



Motor PTC



Potentiometer

10kOhm

*with SK 220E and SK230E: use GND (Terminal 40)
**with SK 220E and SK230E: use Analog In 2 (Terminal 16) and paramterise P400[02] to {1}