2.8.2

Details of the SK 2x0E control connections

The frequency inverter generates its own control voltage and provides this to Terminal 43.

With size 4 the connection terminals for an electro-mechanical brake are located on a 2-pole terminal block
which is separate from the control terminal strip (Terminal 79/80, see Section 2.7.4).

Terminal/

Name

Function

{Factory setting}

Data

Description / wiring suggestion

Parameter


SK 200E, SK 210E, SK 220E, SK 230E

43

VO/24V

24V supply

Output

24VDC ±25%

max. 200mA (output)

Supply voltage provided by the
frequency inverter for connection to
the digital inputs or the supply of a
10-30V encoder.

-

40

GND/0V

Reference potential
for digital signals

-

21

DIN1

Digital input 1

{ON right}

Digital input as per
EN 61131-2 Type 1

Low: 0-5V

(~ 9.5k

Ω)

High: 15-30V

(~ 2.5-3.5k

Ω)

Input capacitance:
Input 1 + 4 = 10 nF
Input 2 + 3 = 1.2 nF

Scan time: 1ms

Reaction time:

≥ 4ms


HTL encoder connection
only to DIN2 and DIN3
possible
Frequency limits:
max. 205 kHz

min. 250 Hz

43

40

21

22

23
24

24V

GND / 0V

Inputs 1 + 4 react slowly

Inputs 2 + 3 react quickly

P420 [01]

22

DIN2

Digital input 2

{ON left}

P420 [02]

23

DIN3

Digital input 3

{fixed frequency 1,
(P465[-01])}

P420 [03]

24

DIN4

(only SK200/220E)

Digital input 4

{fixed frequency 2,
(P465 [-02])}

P420 [04]

1

DOUT1

Output 1

{Fault}

Digital output

24VDC, max. 20mA

max. 100k

load

For evaluation in a control system.

P434 [01]

3

DOUT2

Output 2

{Fault}

P434 [02]

14

AIN1+

(only SK200/210E)

Analog input 1

{Setpoint frequency}

U=0…10V, R

i

=30kΩ

Resolution 12Bit

I=0…20mA, Burden
resistor (250

Ω) via DIP

switch AIN1/2 (Diagnostic
opening D2, Section 4.1)

11

12

14

16

R=10k

Matching of the analog signals is
performed via P402 and P403.

P400 [01]

16

AIN2+

Analog input 2

{No function}

P400 [02]

12 AGND / 0V

Reference potential
for analogue signals

0V analog
only if SK 200E/SK 210E
present

Use Terminal 40 for
SK 220E/SK 230E

11

10V REF

+ 10V Reference
voltage

+10V, 5mA