3 sk cu4-ioe-, i/o extension, Sk cu4-ioe-, i/o extension – NORD Drivesystems BU0200 User Manual

Page 83

Advertising
background image

SK 200E Manual for frequency inverters

82

Subject to technical alterations

BU 0200 GB-4411

3.4.3

SK CU4-IOE-, I/O extension

The internal I/O units can record sensor and actuator signals. These can be used for a drive function or
forwarded to a host bus system (e.g. Profibus or CANopen).

2x digital inputs

2x analog inputs

1x analog output

Status LEDs: Module status, module error,
Dig In 1, Dig. In 2

DIP switches for selection
0 - 10V, -10 - 10V, 0 - 20mA, 4 - 20mA

DIP switches for: addressing, bus termination

The terminal block of the Customer Unit SK CU4-

IOE… is divided into two potential levels.

NOTE

Looping of the 24V supply or GND is possible, however the maximum current load of 2A
must not be exceeded with theSK CU4-IOE!

12

15

16

11

17

12

13

14

11

40

78

77

C2

C1

40

44

AIN1+

AOUT

24V

GND

Sys+

Sys-

GND A

10V Ref.

Analog input 1

Connection of the 24V supply from
the SK 2xxE

System bus connection

from the SK 2xxE

Potential level:

System bus

Potential level:

analog part

Connection to the

terminal block of the SK CU4-IOE

AIN1-

Analog output

Analog input 2

AIN2+

GND A

10V Ref.

AIN2-

SK CU4-

SK 2xxE-

Similar to illustration