6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

225

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P546

Func. bus-set point 1 ... 3

(Function of bus - setpoint 1 ... 3)

S

P

0 ... 24

{ [-01] = 1 }

{ [-02] = 0 }

{ [-03] = 0 }

In this parameter, a function is assigned to the output setpoint during bus actuation.

NOTE:

For further details, please refer to the relevant bus manual or the description for
(P400). (Values from 0% … 100% correspond to 0000

hex

… 4000

hex

,)

For standardisation of the setpoint values: see also Section 9.11.

[-01] = Bus setpoint value 1

[-02] = Bus setpoint value 2 (only for PPO type 2 or 4)

[-03] = Bus setpoint value 3 (only for PPO type 2 or 4)

Possible setting values:

0 = Off

1 = Setpoint frequency (16 Bit)

2 = Frequency addition

3 = Frequency subtract

"Frequency subtraction"

4 = Minimum frequency

5 = Maximum frequency

6 = Cur val, process ctrl

"Current value, process controller"

7 = Nom val, process ctrl

"Nominal value, process controller"

8 = PI current frequency

9 = PI limited current freq

"PI limited current frequency"

10 = PI suprvsd cur freq

"PI supervised current frequency"

11 = Torque current limit

"Torque current limitation (limited)"

12 = Torqu curr limit off

"Torque current limitation (switch-off)"

13 = Current limit "Current limit (limited)"

14 = Current limit off "Current limit (switch-off)"

15 = Ramp time, (P102/103)

16 = Pre-tension torque ((P214) multiplication)

17 = Multiplication

18 = Curve control

"Curve travel calculator"

19 = Servo mode torque

20 = BusIO InBits 0-7

21 = ..24 reserved for Posicon

31 = Digital output IOE, sets the state of DOUT

of the first IOE

32 = Analog output IOE, sets the value AOUT

of the first IOE, condition:
P418 = Function "31"

P549

Pot Box function

(PotentiometerBox function)

S

0 ... 3

{ 1 }

This parameter provides the possibility of adding a correction value (fixed frequency, analog,
bus) to the current setpoint value by means of the SimpleBox/ParameterBox keyboard.

The adjustment range is determined by the auxiliary setpoint value P410/411.

0 = Off

1 = Setpoint frequency, with (P509)

≠ 1

control via USS is possible

2 = Frequency addition

3 = Frequency subtraction

P550

EEPROM copy order

(EEPROM copy order)

S

0 ... 3

{ 0 }

From Firmware V1.3

The frequency inverter is equipped with an internal EEPROM, which is primarily used for the
storage of fault-relevant data and operating hours. If an external EEPROM "Memory Module" is
not plugged in, the parameter settings are also saved in the internal EEPROM. The data sets
saved in the internal EEPROM and in the Memory Module can be copied between the devices.

0 = No change

1 = External

Internal EEPROM, the

data set is copied from the Memory
Module (external EEPROM) to the
internal EEPROM

2 = Internal

External EEPROM, the

data set is copied from the internal
EEPROM to the Memory Module
(external EEPROM)

3 = Exchange data sets, the data sets are

exchanged between the two EEPROMs

Note: The frequency inverter always uses the data set which is stored in the external
EEPROM (Memory Module). The parameterisation of the internal EEPROM is only used if no
Memory Module is plugged in.