NORD Drivesystems BU0200 User Manual
Page 226

6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
225
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P546
Func. bus-set point 1 ... 3
(Function of bus - setpoint 1 ... 3)
S
P
0 ... 24
{ [-01] = 1 }
{ [-02] = 0 }
{ [-03] = 0 }
In this parameter, a function is assigned to the output setpoint during bus actuation.
NOTE:
For further details, please refer to the relevant bus manual or the description for
(P400). (Values from 0% … 100% correspond to 0000
hex
… 4000
hex
,)
For standardisation of the setpoint values: see also Section 9.11.
[-01] = Bus setpoint value 1
[-02] = Bus setpoint value 2 (only for PPO type 2 or 4)
[-03] = Bus setpoint value 3 (only for PPO type 2 or 4)
Possible setting values:
0 = Off
1 = Setpoint frequency (16 Bit)
2 = Frequency addition
3 = Frequency subtract
"Frequency subtraction"
4 = Minimum frequency
5 = Maximum frequency
6 = Cur val, process ctrl
"Current value, process controller"
7 = Nom val, process ctrl
"Nominal value, process controller"
8 = PI current frequency
9 = PI limited current freq
"PI limited current frequency"
10 = PI suprvsd cur freq
"PI supervised current frequency"
11 = Torque current limit
"Torque current limitation (limited)"
12 = Torqu curr limit off
"Torque current limitation (switch-off)"
13 = Current limit "Current limit (limited)"
14 = Current limit off "Current limit (switch-off)"
15 = Ramp time, (P102/103)
16 = Pre-tension torque ((P214) multiplication)
17 = Multiplication
18 = Curve control
"Curve travel calculator"
19 = Servo mode torque
20 = BusIO InBits 0-7
21 = ..24 reserved for Posicon
31 = Digital output IOE, sets the state of DOUT
of the first IOE
32 = Analog output IOE, sets the value AOUT
of the first IOE, condition:
P418 = Function "31"
P549
Pot Box function
(PotentiometerBox function)
S
0 ... 3
{ 1 }
This parameter provides the possibility of adding a correction value (fixed frequency, analog,
bus) to the current setpoint value by means of the SimpleBox/ParameterBox keyboard.
The adjustment range is determined by the auxiliary setpoint value P410/411.
0 = Off
1 = Setpoint frequency, with (P509)
≠ 1
control via USS is possible
2 = Frequency addition
3 = Frequency subtraction
P550
EEPROM copy order
(EEPROM copy order)
S
0 ... 3
{ 0 }
From Firmware V1.3
The frequency inverter is equipped with an internal EEPROM, which is primarily used for the
storage of fault-relevant data and operating hours. If an external EEPROM "Memory Module" is
not plugged in, the parameter settings are also saved in the internal EEPROM. The data sets
saved in the internal EEPROM and in the Memory Module can be copied between the devices.
0 = No change
1 = External
→ Internal EEPROM, the
data set is copied from the Memory
Module (external EEPROM) to the
internal EEPROM
2 = Internal
→ External EEPROM, the
data set is copied from the internal
EEPROM to the Memory Module
(external EEPROM)
3 = Exchange data sets, the data sets are
exchanged between the two EEPROMs
Note: The frequency inverter always uses the data set which is stored in the external
EEPROM (Memory Module). The parameterisation of the internal EEPROM is only used if no
Memory Module is plugged in.