1 overview of optional modules, 1 overview of internal customer units sk cu4, 1 overview of optional modules 3.1.1 – NORD Drivesystems BU0200 User Manual

Page 69

Advertising
background image

SK 200E Manual for frequency inverters

68

Subject to technical alterations

BU 0200 GB-4411

3.1 Overview of optional modules

3.1.1

Overview of internal customer units SK CU4-

Internal customer interfaces enable the expansion of the range of functions of SK 2xxE frequency inverters
without changing the physical size. Either a field bus module, a mains unit or an I/O extension can be
selected. The frequency inverter provides one slot for the fitting of an appropriate option. External options
(technology units) are available for additionally required optional modules (Section 3.2.2).

The bus modules require an external 24V supply, and are therefore also ready for operation if the frequency
inverter is not connected to the mains supply.

Module

Description

Data

Profibus module

SK CU4-PBR

Part No. 275271000

This option enables connection of up to four
SK 2xxE to the Profibus.

Baud rate: 12 MBaud

Protocol: DP-V1

2x digital inputs
Low: 0-5V, High: 11-30V

System bus

CANopen module

SK CU4-CAO

Part No. 275271001

This option enables connection of up to four
SK 2xxE to the CANbus with the CANopen
protocol.

Baud rate: up to 1 MBit/s

Protocol: DS301 / DSP402

2x digital inputs
Low: 0-5V, High: 11-30V

System bus

DeviceNet module

SK CU4-DEV

Part No. 275271002

This option enables connection of up to four
SK 2xxE to DeviceNet.

Baud rate: 500 KBit/s

Protocol: AC-Drive

2x digital inputs
Low: 0-5V, High: 11-30V

System bus

I/O extension

SK CU4-IOE

Part No. 275271006

The internal IO extension provides further digital
and analog inputs and outputs. These are in
addition to the digital inputs provided by the
SK 2xxE (Section 3.4.3).

2x digital inputs
Low: 0-5V, High: 11-30V

2x analog inputs
0-10V, -10-10V, 0-20mA, 4-20mA

1x analog output
0-10V, -10-10V, 0-20mA, 4-20mA

System bus

Potentiometer/Switch

SK CU4-POT *

Part No. 275271207

Internal potentiometer/switch

Can only be used in combination with a 24V
mains unit (SK CU4-24V, SK TU4-24V) or IO
extension (SK CU4-IOE, SK TU4-IOE).

ON R / OFF / ON L

0…100% setpoint potentiometer

10kΩ

Int. 24V mains unit 1~ 230V

SK CU4-24V-123-B

Part No. 275271108

Internal 24V mains unit for supply of the
SK 2x5E, with a mains voltage of
1~ 100-240V, ±10%.

24V=, ±10%, 420mA

10V ref., ±0.2V, 5mA

Analog input 0-10V

Advertising