SK 200E Manual for frequency inverters

224

Subject to technical alterations

BU 0200 GB-4411

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P543

[-01]

...

[-03]

Bus actual value

1… 3

(Actual bus value 1)

S

P

0 ... 24

{ [-01] = 1 }

{ [-02] = 4 }

{ [-03] = 9 }

In this parameter the returned value on bus actuation can be selected.

NOTE:

For further details, please refer to the relevant bus manual or the description for
(P418). (Values from 0% … 100% correspond to 0000

hex

… 4000

hex

)

For standardisation of the actual values: See also (Section 9.10).

[-01] = Actual bus value 1

[-02] = Actual bus value 2 (only for PPO type 2 or 4)

[-03] = Actual bus value 3 (only for PPO type 2 or 4)

(Definition of frequencies, see Section. 9.11)

Possible setting values:

0 = Off

1 = Actual frequency

(x=4000

hex

*f[Hz]/(P105))

2 = Actual speed

(x=4000

hex

*n(rpm]/(P202))

3 = Current

(x=4000

hex

*I[A]/(P203))

4 = Torque current (100% = P112)

(x=4000

hex

*Iq[A]/(P112)*100/

√((P203)²+(P209)²)

5 = Digital IO status

9

6 = ... 7 reserved

8 = Setpoint frequency

(x=4000

hex

*fs[Hz]/(P105))

9 = Error code

10 = ... 11 reserved

12 = Bus IO Out Bits 0..-7

13 = ... 16 reserved

17 = Value analog input 1,

SK2x0E: Analog input 1 (P400[-01]),

SK2x5E: AIN1 of the first I/O extension
SK xU4-IOE (P400 [-03]))

18 = Value analog input 2,

SK2x0E: Analog input 2 (P400[-02]),

SK2x5E: AIN2 of the first I/O extension
SK xU4-IOE (P400 [-04]))

19 = Freq

master value (P503)

"Setpoint frequency master value"

(x=4000

hex

*fs[Hz]/(P105))

20 = Set freq after ramp ,

"Setpoint frequency from ramp master
value"

(x=4000

hex

*fsnr[Hz]/(P105))

21 = Act. freq. wo. slip,

"Actual frequency without slip master
value"

(x=4000

hex

*f-f2[Hz]/(P105))

22 = Speed encoder

"Speed from encoder"

(x=4000

hex

*n[rpm]/(P201)*(60/p))

p=number of pole pairs

23 = Actual with slip

(SW V1.3 and above)

"Actual frequency with slip"

(x=4000

hex

*f[Hz]/(P105))

24 = Master actual

(SW V1.3 and above)

"Actual frequency master value with slip"

(From SW V1.3)

(x=4000

hex

*f[Hz]/(P105))

9

The assignment of the dig. inputs for P543 = 5

Bit 0 = DigIn 1

(FI)

Bit 1 = DigIn 2

(FI)

Bit 2 = DigIn 3

(FI)

Bit 3 = DigIn 4

(FI)

Bit 4 = PTC input

(FI)

Bit 5 = DigIn 5

(DI1, 1.

SK…IOE)

Bit 6 = DigIn 6

(DI2, 1. SK…IOE)

Bit 7 = DigIn 7

(DI3, 1. SK…IOE)

Bit 8 = DigIn 8

(DI4, 1.

SK…IOE)

Bit 9 = reserved

Bit 10 = reserved

Bit 11 = reserved

Bit 12 = DigOut 1

(FI)

Bit 13 = mech. brake

(FI)

Bit 14 = DigOut 2

(DO1, 1.

SK…IOE)

Bit 15 = DigOut 3

(DO2, 1. SK…IOE)