NORD Drivesystems BU0200 User Manual

Page 264

Advertising
background image

7 Status messages

BU 0200 GB-4411

Subject to technical alterations

263

Display in the
SimpleBox

Error

Text in the Parameter Box

Cause

Remedy

Group

Details in
P700[-01] /
P701

E010

10.0

Bus timeout

(Telegram timeout /
Bus off 24V int. CANbus)

Data transfer is faulty. Check P513.

Check external bus connection.

Check bus protocol program process.

Check Bus master.

Check 24V supply of internal CAN/CANopen Bus.

Nodeguarding error (internal CANopen)

Bus Off error (internal CANbus)

10.2

Bus timeout Option

(External bus module telegram
time-out)

Telegram transfer is faulty.

Check external connection.

Check Bus Protocol program process.

Check Bus master.

10.4

Initiation error, Option

(External bus module
initialisation failure)

Check Bus module current supply.

DIP switch setting of a connected I/O extension module is
incorrect

10.1

System error, Option

(Bus module)

Further details can be found in the relevant additional BUS
operating instructions.

I/O extension:

Incorrect measurement of the input voltage or undefined
provision of the output voltage due to error in reference
voltage generation.

Short circuit at analog output

10.3

10.5

10.6

10.7

10.9

Missing Option /P120

Module entered in P120 is not available.

E011

11.0

Control terminals
(Customer Unit)

(analog/digital converter error)

Internal Customer Unit (internal data bus) faulty or disturbed
by radio emissions (EMC).

Check control terminals connection for short-circuit.

Minimise EMC interference through separate laying of
control and power cables.

Device and shielding must be well earthed.