6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

217

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P525

[-01]

...

[-03]

Load control max

(Load monitoring maximum value)

S

P

1 ... 400 % / 401

{ all 401 }

From Firmware V1.3

Selection of up to 3 auxiliary values:

[-01] = Auxiliary value 1

[-02] = Auxiliary value 2

[-03] = Auxiliary value 3

Maximum load torque value.

Setting of the upper limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the values are processed (motor / generator torque, right/left rotation).
The array elements [-01], [-02] and [-03] of parameters (

P525) … (P527), or the entries which

are made there always belong together.

401 = OFF Means that the function is switched off. No monitoring is performed. This is also

the basic setting for the FI.

P526

[-01]

...

[-03]

Load control min

(Load monitoring, minimum value)

S

P

0 ... 400 %

{ all 0 }

From Firmware V1.3

Selection of up to 3 auxiliary values:

[-01] = Auxiliary value 1

[-02] = Auxiliary value 2

[-03] = Auxiliary value 3

Minimum load torque.

Setting of the lower limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the values are processed (motor / generator torque, right/left rotation).
The array elements [-01], [-02] and [-

03] of parameters (P525) … (P527), or the entries which

are made there always belong together.

0 = OFF

Means that the function is switched off. No monitoring is performed. This is also

the basic setting for the FI.

P527

[-01]

...

[-03]

Load control freq.

(Load monitoring frequency)

S

P

0.0 ... 400.0 Hz

{ all 25.0 }

From Firmware V1.3

Selection of up to 3 auxiliary values:

[-01] = Auxiliary value 1

[-02] = Auxiliary value 2

[-03] = Auxiliary value 3

Auxiliary frequency values

Definition of up to 3 frequency points, which define the monitoring range for load monitoring.
The auxiliary frequency values do not need to be entered in order of size. Prefixes are not
taken into account, only the integer values are processed (motor / generator torque, right/left
rotation). The array elements [-01], [-02] and [-

03] of parameters (P525) … (P527), or the

entries which are made there always belong together.