SK 200E Manual for frequency inverters

152

Subject to technical alterations

BU 0200 GB-4411

Details of DIP switch S1: 5/4 and 3

Applies to devices SK 20xE, SK 21xE (without on board AS interface)

DIP

Functions as per the list of digital functions (P420)

Functions as per the list of

analog functions (P400)

5

4

3

Dig 1

Dig 2

Dig 3

Dig 4**

Poti 1***

Poti 2***

off

off

off

(P420 [01])*

{01}

"Enable R"

(P420 [02])*

{02}

"Enable L"

(P420 [03])*

{04}

“Fixed freq. 1"

=5Hz (P465[01])

(P420 [05])*

{04}

“Fixed freq. 2"

=10Hz (P465[02])

(P400 [01])*

{01}

" F setpoint"

(P400 [02])*

{15}

"Ramp"

off

on

off

{01}

"Enable R"

{02}

"Enable L"

{26}

"F setpoint"

{12}

"Quit"

{05}

"F max"

{04}

"F min"

on

off

off

{45}

"3-on"

{49}

"3-off"

{47}

"Freq. +"

{48}

"Freq. -"

{05}

"F max"

{15}

"Ramp"

on

on

off

{50}

„F Arr Bit0

=5Hz (P465[01])

{51}

„F Arr Bit1“

=10Hz (P465[02])

{52}

„F Arr Bit2“

=20Hz (P465[03])

{53}

„F Arr Bit3“

=35Hz (P465[04])

{05}

"F max"

{15}

"Ramp"

off

off

on

The functions of the digital inputs are inactive (control via system bus), however, the
settings made in parameters (P420 [01 … 04]) result in the activation of the
correspondingly parameterised input, for the functions designated with ..² in the function
list (e.g.: {11}²= "Quick stop).

(P400 [01])

{

01} " F setpoint"

(P400 [02])

{15}

"Ramp"

(P420 [01])

no function

(P420 [02])

no function

(P420 [03])

{04} Fixed freq. 1"

=5Hz (P465[01])

(P420 [04])

{05} Fixed freq. 2"

=10Hz (P465[02])

off

on

on

{14}

"Remote

control"

"Encoder track
A"

"Encoder track
B"

{01}

"Enable R"

{01}

"F

setpoint"

{05}

"F max"

on

off

on

{14}

"Remote

control"

{01}

"Enable R"

{10}

"Block"

{66}

"Release

brake"

{01}

"F

setpoint"

{05}

"F max"

on

on

on

{14}

"Remote

control"

{51}

„F Arr Bit1“

=10Hz (P465[02])

{52}

„F Arr Bit2“

=20Hz (P465[03])

{53}

„F Arr Bit3“

=35Hz (P465[04])

{05}

"F max"

{15}

"Ramp"

Explanation: (values underlined in brackets) = (relevant parameter / source of function), e.g.: Parameter (P420[01])

{curly brackets}

= {Function} e.g.: {01} "Enable Right"

(See also Section 6

: → Table behind parameter (P420), (P400) or (P434))

* Default setting

** only if available (Devices without function "Safe Stop")

*** only with SK 2x5E models, SK 2x0E models have no potentiometers P1 and P2

Applies to devices SK 22xE, SK 23xE (with on board AS interface)

DIP

Functions as per the list of digital functions (P420)

Functions as per the list of digital outputs (P434)

5

4

3

ASi

In1

ASi

In2

ASi

In3

ASi

In4

ASi

Out1

ASi

Out2

ASi

Out3

ASi

Out4

off off off

(P480 [01])*

{01}

"Enable

R"

(P480 [02])*

{02}

"Enable

L"

(P480 [03])

{04}

Fixed

freq. 1"

=5Hz (P465[01])

(P480 [04])*

{12}

"Quit"

(P481 [01])*

{07}

"Error"

(P481 [02])*

{18}

"Standby"

"DigIn1"

"DigIn2"

off on off

{04}

"Fixed

freq. 1"

=5Hz (P465[01])

{05}

"Fixed

freq. 2"

=10Hz (P465[02])

{06}

"Fixed

freq. 3"

=20Hz (P465[03])

{07}

"Fixed

freq. 4"

=35Hz (P465[04])

{07}

"Error"

{18}

"Standby"

"DigIn1"

"DigIn2"

on off off

{01}

"Enable R"

{02}

"Enable L"

{47}

"Freq. +"

{48}

"Freq. -"

{07}

"Error"

{18}

"Standby"

"DigIn1"

"DigIn2"

on on off

{51}

"F Arr B1"

=10Hz (P465[02])

{52}

"F Arr B2"

=20Hz (P465[03])

{53}

"F Arr B3"

=35Hz (P465[04])

{14}

"Remote

control"

{07}

"Error"

{18}

"Standby"

"DigIn1"

"DigIn2"

off off on

The functions of the digital inputs are inactive (control via system bus),
however, the settings made in parameters (P480 [01 … 04]) result in the
activation of the correspondingly parameterised bits, for the functions
designated with ..² in the function list (e.g.: {11}²= "Quick stop).

(P481 [01])

{07}

"Error"

(P481 [02])

{18}

"Standby"

"DigIn1"

"DigIn2"

(P480 [01])no
function

(P480 [02])

no function

(P480 [03])

{04}

Fixed

freq. 1"

=5Hz (P465[01])

(P480 [04])

{12}

"Quit"

off on on

{14}

"Remote

control"

{04}

"Fixed

freq. 1"

=5Hz (P465[01])

{05}

"Fixed

freq. 2"

=10Hz (P465[02])

{06}

"Fixed

freq. 3"

=20Hz (P465[03])

{07}

"Error"

{18}

"Standby"

"DigIn1"

"DigIn2"

on off on

{14}

"Remote

control"

{01}

"Enable R"

{47}

"Freq. +"

{48}

"Freq. -"

{07}

"Error"

{18}

"Standby"

"DigIn1"

"DigIn2"

on on on

{14}

"Remote

control"

{50}

"F Arr B0"

=5Hz (P465[01])

{51}

"F Arr B1"

=10Hz (P465[02])

{52}

"F Arr B2"

=20Hz (P465[03])

{07}

"Error"

{18}

"Standby"

"DigIn1"

"DigIn2"

Explanation: See table above

Note:

The functions of potentiometers P1 and P2 correspond to those of devices without an AS interface (see table above).

With DIP switches 5 and 4 in the OFF position (default setting), the digital inputs are also active. The functions then correspond to those of devices
without an AS interface (table above). In all other DIP switch combinations the functions of the digital inputs are deactivated.
ASi OUT1 and ASi OUT2 loop the signal level (High / Low) of digital inputs 1 and 2.