Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P219

Auto. magn. adjustment

(Automatic magnetisation adjustment)

S

25 ... 100 % / 101

{ 100 }

With this parameter, an automatic adjustment of the magnetic flux to the motor load can be
made. P219 is a limiting value, to which the field in the motor can be reduced.

As standard, the value is set to 100%, and therefore no reduction is possible. As minimum, 25%
can be set.

The reduction of the field is performed with a time constant of approx. 7.5 sec. On increase of
load the field is built up again with a time constant of approx. 300 ms. The reduction of the field
is carried out so that the magnetisation current and the torque current are approximately equal,
so t

hat the motor is operated with “optimum efficiency”. An increase of the field above the

setpoint value is not intended.

This function is intended for applications in which the required torque only changes slowly (e.g.
pumps and fans). Its effect therefore replaces a quadratic curve, as it adapts the voltage to the
load.

NOTE:

This must not be used for lifting or applications where a more rapid build-up of the
torque is required, as otherwise there would be overcurrent switch-offs or inversion
of the motor on sudden changes of load, because the missing field would need to
be compensated by a disproportionate torque current.

101 = automatic, with the setting P219=101 an automatic magnetisation current controller is

activated. The ISD controller then operates with a subordinate magnetizing controller,
which improves the slippage calculation, especially at higher loads. The control times
are considerably faster compared to the Normal ISD control (P219 = 100)

P2xx

Control/characteristic curve parameters

NOTE: "typical"

P211

P210

P204

P201

P216

P215

Output

voltage

Output frequency

Time

settings for the...

Current vector control (factory setting)

P201 to P209 = Motor data

P210 = 100%

P211 = 100%

P212 = 100%

P213 = 100%

P214 = 0%

P215 = no significance

P216 = no significance

Linear V/f characteristic curve

P201 to P209 = Motor data

P210 = 100% (static boost)

P211 = 0%

P212 = 0%

P213 = no significance

P214 = no significance

P215 = 0% (dynamic boost)

P216 = 0s (time dyn. boost)