3 Options

BU 0200 GB-4411

Subject to technical alterations

109

3.5.4.3

Signal status LEDs

The definition of the LED signals of the external I/O extension (SK TU4-IOE-

…) corresponds to that for the

internal I/O - extension SK CU4-IOE. The appropriate details are described in Section 3.4.3.3.


Exception: The signal statuses of the digital inputs and outputs (DI … / DO …) are only visualised with the
M12 version (SK TU4-IOE-M12) (See also Section 3.5.4 "Details of the M12 connections of the
SK TU4-IOE-M12").

I/O displays

I/O channel

Status display

Meaning

LED (yellow)

Digital input 1

DI1

ON

High potential on terminal 19 or the M12 socket DI1

OFF

Low potential on terminal 19 or the M12 socket DI1

Digital input 2

DI2

ON

High potential on terminal 25 or the M12 socket DI2

OFF

Low potential on terminal 25 or the M12 socket DI2

Digital input 3

DI3

ON

High potential on terminal 20 or the M12 socket DI3

OFF

Low potential on terminal 20 or the M12 socket DI3

Digital input 4

DI4

ON

High potential on terminal 26 or the M12 socket DI4

OFF

Low potential on terminal 26 or the M12 socket DI4

Digital output 1

DO1

ON

High potential on terminal 33 or the M12 socket DO1

OFF

Low potential output to terminal 33 or the M12 socket DO1

Digital output 2

DO2

ON

High potential on terminal 34 or the M12 socket DO1

OFF

Low potential output to terminal 34 or the M12 socket DO1

3.5.4.4

Termination resistor, addressing, assignment of functions, broadcast mode

The internal and external I/O extensions have identical functions, insofar as the procedure for configuration,
addressing etc. of the SK TU4-IOE-

… is carried out as for the SK CU4-IOE-…. (For details, see Sections

3.4.3.4 to 3.4.3.7).