SK 200E Manual for frequency inverters

90

Subject to technical alterations

BU 0200 GB-4411

3.4.5

CANopen, SK CU4-CAO

Up to four connected frequency inverters can be managed by the internal CANopen module via CANopen
(control, status messages, parameterisation and diagnosis).

Baud rate: max. 1 MBaud

Protocol: DS301 and DSP 402 1

2x digital inputs

DIP switches for: addressing, bus termination,
baud rate

Status LEDs: Module status, module error,
bus status, bus error, Dig. In 1, Dig. In 2

The terminal block of the Customer Unit SK CU4-CAO is divided into two potential levels.

The field bus level is electrically isolated from the system bus level and must therefore be separately
supplied with 24VDC.

Up to 2 sensors can be connected via the terminal block (terminals C1 and C2).

NOTE

Looping of the 24V supply or GND is possible, however the maximum current load of 2A
must not be exceeded with theSK CU4-CAO!

Detailed information for operation via CANopen can be found in the relevant supplementary manual BU0260.

-

www.nord.com

-

46

76

75

45

90

46

76

75

45

40

78

77

C2

C1

40

44

CANopen-

CANopen+

CANopen-

CANopen+

24V

GND

Sys+

Sys-

GND B

GND B

24V B

Incoming
CANopen cable

Outgoing
CANopen cable

Connection of the 24V power
supply from the SK 2xxE

System bus connection

from the SK 2xxE

SHLD

Potential level:

System bus

Potential level:

Field bus

Connection to the

terminal block of the SK CU4-CAO

SK CU4-

SK 2xxE-

Similar to illustration