6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

195

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P401

[-01]

...

[-06]

Mode analog in

(Mode analog input)

S

0 ... 5

{ all 0 }

... only with
SK CU4-IOE or
SK TU4-IOE

as of SW 1.2

[-01] = Ext analog in 1, "External analog input 1", AIN1 of the first I/O extension (SK xU4-IOE).

[-02] = Ext analog in 2, "External analog input 2", AIN2 of the first I/O extension (SK xU4-IOE).

[-03] = Ext. A.in 1 2nd IOE, "External analog input 1 2nd IOE", AIN1 of the second I/O

extension (SK xU4-IOE) (= analog input 3).

[-04] = Ext. A.in 2 2nd IOE, "External analog input 2 2nd IOE", AIN1 of the second I/O

extension (SK xU4-IOE) (= analog input 4).

[-05] = Analog input 1, Analog input1 (only SK 200E, SK 210E)

[-06] = Analog input 2, Analog input 2 (only SK 2x0E)

0 = 0

– 10V limited: An analog setpoint smaller than the programmed adjustment 0%

(P402), does not result in an undershooting of the programmed minimum frequency
(P104), i.e. does not result in a reversal of the direction of rotation.

1 = 0

– 10V: If there is a setpoint value which is smaller than the programmed adjustment

0% (P402), this may result in a change in the direction of rotation. Because of this, a
reversal of the direction of rotation may be implemented with a simple voltage source
and a potentiometer.

e.g. internal setpoint with change of direction of rotation: P402 = 5V, P104 = 0Hz,
potentiometer 0

–10V  change of direction of rotation at 5V in the middle setting of the

potentiometer.

At the moment of reversal (Hysteresis =

P505), the drive unit is at a standstill, if the

minimum frequency (P104) is less than the absolute minimum frequency (P505). A
brake controlled by the FI is applied within the hysteresis range.

If the minimum frequency (P104) is larger than the absolute minimum frequency
(P505), the drive reverses when the minimum frequency is reached. Within the
hysteresis range

P104 provides the FI with the minimum frequency (P104), a brake

controlled by the FI is not applied.

2 = 0

– 10V control

l

ed: If the minimum

adjusted setpoint value (P402) is
undershot by 10% of the difference
between (P403) and (P402), the FI
output switches off. As soon as the
setpoint value is larger than
[P402 - (10% * (P403 - P402))], it
once again provides an output signal.

f / Hz

P104

(fmin)

P105

(fmax)

P

4

0

3

=

1

0

.0

V

P

4

0

2

=

2

.0

V

= 8.0V

U/V

O

F

F

=

2

.0

V

-

1

0

%

*

8

.0

V

=

1

.2

V

E.g.: Setpoint value 4-20mA: P402: Adjustment 0% = 1V; P403: Adjustment 100% = 5V;
-10% corresponds to -0.4V; i.e. 1...5V (4...20mA) normal operating range, 0.6...1V =
minimum frequency setpoint value, below 0.6V (2.4mA) the output is switched off.