NORD Drivesystems BU0200 User Manual

Page 281

Advertising
background image

SK 200E Manual for frequency inverters

280

Subject to technical alterations

BU 0200 GB-4411

Size 4

Device type:

SK 2x0E…

-112-340-A

-152-340-A

-182-340-A

-222-340-A

Nominal motor power

(4-pole standard motor)

400V

11.0 kW

15.0 kW

18.0 kW

22.0 kW

480V

15 hp

20 hp

25 hp

30 hp

In

p

u

t

Mains voltage

3~ 400V

3 AC 380 ... 500V, -20 / + 10%, 47 ... 63 Hz

Typical input current
at 400V

3~ rms

23.6 A

32.0 A

40.5 A

46.5 A

3~ FLA

20.5 A

28.0 A

35.5 A

42.5 A

Rec. mains fuse

1 AC

slow-acting [A]

35 A

50 A

50 A

63 A

Permissible
mains fuses (UL)

RK5 or faster

fuses,

min 230V/400V

30 A

40 A

60 A

60 A

Bussmann

FRS-R-30

FRS-R-40

FRS-R-60

FRS-R-60

Circuit breaker*

min. 230V/400V

30 A

40 A

60 A

60 A

O

u

tp

u

t

Output voltage

3~ 400V

3 AC 0 - Mains voltage

Nominal output cur-
rent at 400V

rms

23.0 A

32.0 A

40.0 A

46.0 A

Motor Assem-

bly**

23.0 A

32.0 A

40.0 A

46.0 A

Wall-mounted**

23.0 A

29.0 A

40.0 A

46.0 A

Min. braking resistor

47

33

27

24

Recommended braking
resistor

Sec. 2.3

100

100

50

50

Motor Assembly

Max. continuous power / max. continuous current:

S1-50℃

S1-40°C

11.0 kW / 23 A

11.0 kW / 23 A

15.0 kW / 32 A

15.0 kW / 32 A

15.0 kW / 29 A

18.5 kW / 40 A

15.0 kW / 29 A

22.0 kW / 40 A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

50°C

50°C

50°C

50°C

50°C

50°C

45°C

46°C

46°C

40°C

42°C

42°C

Wall-mounting

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

11.0 kW / 23 A

11.0 kW / 23 A

15.0 kW / 32 A

15.0 kW / 32 A

15.0 kW / 29 A

18.5 kW / 40 A

15.0 kW / 29 A

22.0 kW / 40 A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

50°C

50°C

50°C

50°C

50°C

50°C

45°C

46°C

47°C

40°C

42°C

42°C

* Circuit Breaker (inverse time trip type) as per UL489

** FLA (S1-40 °C)