3 Options

BU 0200 GB-4411

Subject to technical alterations

125

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

21

0V

22

GND
Reference potential
for digital signals

As for terminal 15

Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 to DIN8)

-

23 24V

24

24V supply

(Module and system bus
level)

As for terminal 1

However, max.
permissible current load:
3A

-

25

DIN2

Digital input 2

(I/O EtherCAT DIN2)

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF
Scan rate 1 ms

Inputs as per
EN 61131-2

Type 1

Each digital input has a reaction
time of 1ms.

P174

26

DIN4

Digital input 4

(I/O EtherCAT DIN4)

P174

27

0V

28

GND
Reference potential
for digital signals

As for terminal 15

Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 to DIN8)

-

29 24V

30

24V supply

(Module and system bus
level)

As for terminal 1

However, max.
permissible current load:
3A

-

Potential isolation

31

24V2

24V supply
of digital outputs

24VDC -/+20%

Up to 1A, according to
load
reverse polarity protected

Supply voltage connection for
digital outputs (DO1 and DO2)

If necessary, bridge to

24V

terminal

-

32

0V2

GND 2
Reference potential
for digital outputs

Ground for digital outputs (DO1
and DO2)

If necessary, bridge to

0V

terminal

-

33

DO1

Digital output 1

(I/O EtherCAT DO1)

Low = 0V
High: 24V

Rated current: 500mA
each

The digital outputs should be used
with a separate 24V supply

P150
P175

34

DO2

Digital output 2

(I/O EtherCAT DO2)

P150
P175

35

0V2

36

GND 2
Reference potential
for digital outputs

Ground for digital outputs (DO1
and DO2)

If necessary, bridge to

0V

terminal

-

Detailed information for operation via EtherCat can be found in the relevant supplementary manual BU0270.

-