NORD Drivesystems BU0200 User Manual

Page 117

Advertising
background image

SK 200E Manual for frequency inverters

116

Subject to technical alterations

BU 0200 GB-4411

Details of the control connections

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

1

24V-B

2

24V bus supply

(field bus)

24VDC -/+20%

≈ 500mA
protected against reverse
polarity


Max. permissible current
load: 500mA

Supply voltage for the CANopen
controller / field bus

-

3

CAN+

(incoming)

4

(outgoing)

Bus +

CAN H

RS485 transfer
technology

The use of a twisted, shielded two-
wire cable is strongly
recommended

-

5

CAN-

(incoming)

6

(outgoing)

Bus -

CAN L

-

7

0V-B

8

Data ground Bus

BUS reference potential

-

9

SHLD

Bus shield

-

10

PE

PE-Bus

-

Potential separation

11

24V

12

13

24V supply

(module, system bus level)

24VDC -/+20%

≈ 500mA
protected against reverse
polarity


Max. permissible current
load: 3A

Connection for module supply
voltage and 24V source for the
digital inputs (DIN1 to DIN4)

-

15

0V

17

18

GND
Reference potential
for digital signals

-

14

Sys+

System bus
data cable +

System bus
interface

-

16

Sys-

System bus
data cable -

-

19

DIN1

Digital input 1

(I/O CANopen DIN1)

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF
Scan rate 1ms

Each digital input has a reaction
time of 1ms

Inputs compliant with
EN 61131-2,

Type 1

P174

20

DIN3

Digital input 3

(I/O CANopen DIN3)

P174