SK 200E Manual for frequency inverters

192

Subject to technical alterations

BU 0200 GB-4411

6.1.5

Control clamps

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P400

[-01]

...

[-09]

Fnct. setpoint inputs

(Function of setpoint inputs)

SK 2x0E

P

0 ... 33

{ [-01] = 1 }

{ [-02] = 0 }

{ [-03] = 0 }

{ [-04] = 0 }

{ [-05] = 1 }

{ [-06] = 0 }

a)

{ [-06] = 1 }

b)

{ [-07] = 1 }

a)

{ [-07] = 15 }

b)

{ [-08] = 0 }

{ [-09] = 0 }

SK

2x0E S 1 … 3

a)

SK2x0E S 4

b)

[-01] = Analog input 1, Function of analog input 1 integrated into the FI

[-02] = Analog input 2, Function of analog input 2 integrated into the FI

[-03] = Ext. analog input 1, AIN1 of the first I/O extension (SK xU4-IOE)

[-04] = Ext. analog input 2, AIN2 of the first I/O extension (SK xU4-IOE)

[-05] = Setpoint module, in preparation

[-06] = Digital input 2, can be set to pulse signal

evaluation via P420 [-02] =26 or 27. The
pulses are then evaluated in the FI as an
analog signal according to the function
which is set here.

[-07] = Digital input 3, can be set to pulse signal

evaluation via P420 [-03] =26 or 27. The
pulses are then evaluated in the FI as an
analog signal according to the function
which is set here.

[-06] = Potentiometer 1, Function of

the potentiometer P1 integrated
into the FI (Section 5.2.2). DIP
switches 4/5 must be "Off"
(Section 5.2.2), in order that the
function can be influenced by
this parameter setting

[-07] = Potentiometer 2, as for

potentiometer 1.

[-08] = Ext. A.in 1 2nd IOE, "External analog input 1 2nd IOE", AIN1 of the second I/O

extension (SK xU4-IOE) (= Analog input 3)

[-09] = Ext. A.in 2 2nd IOE, "External analog input 2 2nd IOE", AIN2 of the second I/O

extension (SK xU4-IOE) (= Analog input 4)

... setting values below.

P400

[-01]

...

[-09]

Fnct. setpoint inputs

(Function of setpoint inputs)

SK 2x5E

P

0 ... 33

{ [-01] = 1 }

{ [-02] = 15 }

{ [-03] = 0 }

{ [-04] = 0 }

{ [-05] = 1 }

{ [-06] = 0 }

{ [-07] = 1 }

{ [-08] = 0 }

{ [-09] = 0 }

[-01] = Potentiometer 1, Function of the potentiometer P1 integrated into the FI (Section

5.2.2). DIP switches 4/5 must be "Off" (Section 5.2.2), in order that the function can be
influenced by this parameter setting

[-02] = Potentiometer 2, as for potentiometer 1

[-03] = Ext. analog input 1, AIN1 of the first I/O extension (SK xU4-IOE)

[-04] = Ext. analog input 2, AIN2 of the first I/O extension (SK xU4-IOE)

[-05] = Setpoint module, in preparation

[-06] = Digital input 2, can be set to pulse signal evaluation via parameter P420 [-02] =26 or

27. The pulses are then evaluated in the FI as an analog signal according to the
function which is set here.

[-07] = Digital input 3, can be set to pulse signal evaluation via parameter P420 [-03] =26 or

27. The pulses are then evaluated in the FI as an analog signal according to the
function which is set here.

[-08] = Ext. A.in 1 2nd IOE, "External analog input 1 2nd IOE", AIN1 of the second I/O

extension (SK xU4-IOE) (= Analog input 3)

[-09] = Ext. A.in 2 2nd IOE, "External analog input 2 2nd IOE", AIN2 of the second I/O

extension (SK xU4-IOE) (=Analog input 4)