SK 200E Manual for frequency inverters

138

Subject to technical alterations

BU 0200 GB-4411

Functions of the ParameterBox

LCD

display

Graphic-capable, backlit LCD display for displaying operational values and parameters for the
connected frequency inverter and ParameterBox parameters.

The menu levels and the individual menu items can be scrolled through with the SELECTION keys.

The next higher level can be accessed by pressing the keys

and

at the same time.

The contents of individual parameters can be altered with the VALUES keys.

Press the

and

keys together to load the default values of the parameter selected.

When controlling the inverter using the keyboard, the frequency setpoint is set using the VALUE keys.
Here the ramp time is limited to 0.17s/Hz, even if small values are set in P102/P103.

OK

Press the OK key to change to the selected menu group or accept the changed menu items or
parameter values.

NOTE:

If a parameter is to be exited, without a new value being stored, then one of the
SELECTION keys can be used for this purpose.

If the inverter is currently controlled from the keyboard (not control terminals), then the current actual
frequency can be stored under the Jog Frequency parameter P113 with the OK key and used as the
next initial setpoint frequency.

START key for switching on the frequency inverter.

NOTE:

These functions can
only be used of they
are

enabled

in

parameter

P509

or

P540.

STOP key for switching off the frequency inverter.

The direction of rotation of the motor changes when the DIRECTION key is
operated
. Rotation direction left is indicated by a minus sign.

Attention! Take care when operating pumps, screw conveyors, fans, etc.

LEDs

DS

DE

The LED's indicate the actual status of the ParameterBox.

DS

– Device State

The ParameterBox is ready for operation.

DE

– Device Error

An error has occurred when processing data, or in the FI.

LCD display



205E 1.1kW / 400V

1

Fi/Hz

U/V

I/A

45.0

360

2.4

ONLINE

FI

P1 R RUNNING

Frequency inverter type

Connection to

frequency inverter

Frequency inverter status

Frequency inverter

power, voltage

Current operating values

Frequency, voltage,

current

Operating parameter set