2 parameterisation of i/o - extension sk xu4-ioe, 1 basic parameters (i/o - extension) – NORD Drivesystems BU0200 User Manual

Page 239

Advertising
background image

SK 200E Manual for frequency inverters

238

Subject to technical alterations

BU 0200 GB-4411

6.2 Parameterisation of I/O - extension SK xU4-IOE-

In order to access the parameters of the I/O extension, the parameterisation tool (ParameterBox,
SimpleBox, NordCon) must be connected directly to the device.

If the I/O extension is on an active system bus, it can be accessed with the ParameterBox SK PAR-3H or
the NORD CON software as well as via another device (e.g. frequency inverter SK 2xxE). After the bus
scan, it is only necessary to select the I/O extension (menu item SK PAR-3H: "Object selection").

6.2.1

Basic parameters (I/O - extension)

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P150

Set relays

(Set relays)

SK TU4-IOE

0 ... 4

{ 0 }

The switching statuses of the digital outputs (only SK TU4 IOE) can be changed.

0 = Via bus: all digital outputs are controlled via the system bus, the functions are defined in

the frequency inverter (P480)

1 = Outputs Off: all digital outputs are off (Low = 0V)

2 = Output 1 on (DO1): digital output DO1 is set to "High" (active), digital output DO2

remains switched off

3 = Output 2 on (DO1): digital output DO2 is set to "High" (active), digital output DO1

remains switched off

4 = Outputs 1 and 2 on: all digital outputs are set to "High" (active)

P152

Factory setting

(Factory setting)

0 ... 2

{ 0 }

By selecting the appropriate value and confirming it with the OK key, the selected parameter
range is entered in the factory setting. Once the setting has been made, the value of the
parameter automatically returns to 0.

0 = No change:Does not change the parameterisation.

1 = Load

factory

setting: The complete parameterisation of the FI reverts to the factory

setting. All originally parameterised data is lost.

2 = Calibration AOUT: The accuracy of the analog output can be improved with a correction

line, however, this is not activated as standard. If factory settings (P152={ 1 }) are
loaded, the correction values are retained. A calibration is carried out if (P152) is set to
{ 2 }, i.e. the line is re-recorded and stored in the EEPROM.

P153

[-01]

[-02]

Minimum system bus cycle

(Minimum system bus cycle time)

0 ... 250.00 ms

{ [-01] = 10 }

{ [-02] = 5 }

To reduce the load on the system bus, the transmission cycle time of the service data objects
and process data objects may be increased.

[-01] = SDO Inhibit Time

[-02] = PDO Inhibit Time

P160

Set analog out

(Set analog output)

-0.1 ... 10.0 V

{ -0.1 }

The analog output can output a defined value, which is independent of the system bus.

-0.1

= Control voltage via system bus

0.0 …. 10.0 = Voltage value in V

Advertising