6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

213

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P506

Automatic acknowled.

(Automatic error acknowledgement)

S

0 ... 7

{ 0 }

In addition to the manual error acknowledgement, an automatic acknowledgement can also be
selected.

0 = No automatic error acknowledgement

1 =

1 ... 5 = Number of permissible automatic error acknowledgments within one mains-on

cycle. After mains off and switch on again, the full amount is again available.

6 = always, an error message will be acknowledged automatically if the cause of the error

is no longer present.

7 = quit disable (via enable deactivated), acknowlegement is only possible with the OK

key or by switching off the mains. Acknowledgement is not implemented by removing
the enable!

NOTE: If (P428) is parameterised to "ON", parameter (P506) "Automatic error

acknowledgement" must not be parameterised to setting 6 "Always" as otherwise the
device or system is endangered due to the possibility of continuous restarting in the
case of an active error (e.g. short-circuit to earth / short circuit).

P509

Source Control Word

(Source control word)

S

0 ... 4

{ 0 }

Selection of the interface via which the FI is controlled.

0 = Contr term.

or

keyboard, "Control terminal or keyboard control" ** with the SimpleBox

(if P510=0), the ParameterBox or via BUS I/O Bits.

1 = Contr terminal only, "Control terminals only" *, the FI can only be controlled via the

digital and analog input signals or via the Bus I/O Bits.

2 = USS*, the control signals (enable, rotation direction, etc.) are transferred via the RS485

interface, the setpoint via the analog input or the fixed frequencies.

3 = System bus*

4 = System bus broadcast *

*)

Keyboard control (SimpleBox, ParameterBox, PotentiometerBox) is blocked,
parameterisation is still possible.

**) If the communication during keyboard control is interrupted (time out 0.5 sec), the

FI will block without an error message.

NOTE:

For details of the optional bus systems, please refer to the relevant supplementary bus
manuals (BU02x0).

-

www.nord.com

As an alternative to parameterisation, switchover to system bus broadcast can also be made
via DIP switch 3.

P510

[-01]

[-02]

Source setpoints

(Source setpoints)

S

0 ... 4

{ [-01] = 0 }

{ [-02] = 0 }

Selection of the setpoint source to be parameterised.

[-01] = Source, main setpoint value

[-02] = Source, 2

nd

(auxiliary) setpoint value

Selection of the interface via which the FI receives the setpoint.

0 = Auto: The source of the auxiliary setpoint is

automatically derived from the setting in the
parameter P509 >Interface<

1 = Control terminals only, digital and analog inputs

control the frequency, including fixed frequencies

2 = USS

3 = System bus

4 = System bus broadcast