NORD Drivesystems BU0200 User Manual

Page 237

Advertising
background image

SK 200E Manual for frequency inverters

236

Subject to technical alterations

BU 0200 GB-4411

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P748

Status CANopen

(CANopen status (system bus status))

0000 ... FFFF

(hex)

or

0 ... 65535

(dec)

Displays the system bus status.

Bit 0:

Bit 1:

Bit 2:

Bit 3:

Bit 4:

Bit 5:

Bit 6:

Bit 7:

Bit 8:

Bit 9:

Bit 10:

24V Bus supply voltage

CANbus in "Bus Warning" status

CANbus in "Bus Off" status

System bus → Bus module online (field bus module, e.g.: SK xU4-PBR)

System bus → Additional module 1 online (I/O - module, e.g.: SK xU4-IOE)

System bus → Additional module 2 online (I/O - module, e.g.: SK xU4-IOE)

The protocol of the CAN module is 0 = CAN / 1 = CANopen

vacant

"Bootsup Message" sent

CANopen NMT State

CANopen NMT State

CANopen NMT State

Bit 10

Bit 9

Stopped
Pre-Operational
Operational

0
0
1

0
1
0

P749

Status DIP switches

0000 ... 00FF

(hex)

or

0 ... 511

(dec)

Bit 8: from SW1.3

This parameter shows the actual setting of the FI DIP switch "S1" (See Section 5.2.2.2)

Bit 0:

Bit 1:

Bit 2:

Bit 3:

Bit 4:

Bit 5:

Bit 6:

Bit 7:

Bit 8:

DIP switch 1

DIP switch 2

DIP switch 3

DIP switch 4

DIP switch 5

DIP switch 6

DIP switch 7

DIP switch 8

EEPROM (Memory Module)

Bit 8 = 0: plugged in / Bit 8 = 1: not plugged in