NORD Drivesystems BU0200 User Manual

Page 231

Advertising
background image

SK 200E Manual for frequency inverters

230

Subject to technical alterations

BU 0200 GB-4411

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P705

[-01]

...

[-05]

Dc.lnk volt. last er.

(Last link circuit voltage fault 1...5)

S

0 ... 1000 V DC

This parameter stores the link voltage that was being delivered at the time the error occurred.
The values of the last 5 errors are stored.

With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.

P706

[-01]

...

[-05]

P set last error

(Parameter set, last error 1… 5)

S

0 ... 3

This parameter stores the parameter set code that was active when the error occurred. Data for
the previous 5 faults are stored.

With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.

P707

[-01]

...

[-03]

Software-Version

(Software version/ revision)

0.0 ... 9999.9

This parameter shows the software and
revision numbers in the FI. This can be
significant when different FIs are assigned
the same settings.

Array [-03] provides information about any
special versions of the hardware or
software A zero stands for the standard
version.

[-01] = Software version, version number (V1.0)

[-02] = Software revision, revision number (R1)

[-03] = Special version, of the hardware/software

(0.0)

P708

State of digital in.

(Status of digital inputs)

00000 ... 11111

(bin)

or

00 ... 1F

(hex)

Displays the status of the digital inputs in binary/hexadecimal code. This display can be used to
check the input signals.

Bit 0 = Digital input 1

Bit 1 = Digital input 2

Bit 2 = Digital input 3

Bit 3 = Digital input 4

Bit 4 = PTC resistor input

Bit 5 - 7 reserved

First SK xU4-IOE (optional)
Bit 8 = 1st IO extension: Digital input 1
Bit 9 = 1st IO extension: Digital input 2
Bit 10 = 1st IO extension: Digital input 3
Bit 11 = 1st IO extension: Digital input 4

Second SK xU4-IOE (optional)
Bit 12 =
2nd IO extension: Digital input 1
Bit 13 = 2nd IO extension: Digital input 2
Bit 14 = 2nd IO extension: Digital input 3
Bit 15 = 2nd IO extension: Digital input 4

Bits 15-12 Bits 11-8

Bits 7-4

Bits 3-0

Minimum value

0000

0

0000

0

0000

0

0000

0

Binary

hex

Maximum value

1111

F

1111

F

1111

F

1111

F

Binary

hex

SimpleBox:

The binary Bits are converted into a hexadecimal value and displayed.

ParameterBox: The Bits are displayed with increasing values from right to left (binary).

Advertising