SK 200E Manual for frequency inverters

134

Subject to technical alterations

BU 0200 GB-4411

Control with the SimpleBox

The frequency inverter can only be controlled via the SimpleBox, if it has not previously been enabled via
the control terminals or via a serial interface (P509 = 0 and P510 = 0).

If the START key is pressed, the frequency inverter changes to the operating display (selection P001). The
frequency inverter supplies 0Hz or a higher minimum frequency (P104) or jog frequency (P113) which has
been set.

STOP

Store current frequency

as jog frequency

Set frequency = 0Hz

(press simultaneously)

Increase frequency

Change rotation direction

Decrease frequency

START

Parameter set display

Quick stop

(press simultaneously)

Parameter set display:

The LEDs indicate the actual operating parameter set in the operating display (P000) and the current
parameter set being parameterised (

P000). In this case the display is coded in binary form.

The parameter set can also be changed during operation via the parameter P100, if control is by means of
the SimpleBox.

Frequency setpoint:

The current frequency setpoint depends on the setting in the parameters jog frequency (P113) and minimum

frequency (P104). This value can be altered during keyboard operation with the value keys

and

permanently stored in P113 as the jog frequency by pressing the OK key

OK

.

Quick stop:

A quick stop can be triggered by simultaneously pressing the STOP key

and the "Change direction key”

.