6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

211

6.1.6

Extra functions

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P501

Inverter name

(Inverter name)

A…Z

(char)

{ 0 }

Free input of a designation (name) for the device (max. 20 characters). With the the frequency
inverter can be uniquely identified for processing with NordCon software or within a network.

P502

[-01]

...

[-03]

Value Masterfunction

(Value master function)

S

P

0 ... 24

{ all 0 }

Selection of up to 3 master values of a Master for output to a bus system (see P503). The
assignment of these master values to the slave is carried out via (P546).
(for definition of frequencies see Section 9.11):

[-01] = Master value 1

[-02] = Master value 2

[-03] = Master value 3


Selection of possible setting values for master values:

0 = Off

1 = Actual frequency

2 = Actual speed

3 = Current

4 = Torque current

5 = Status Digital IO

6 = ... 7 reserved

8 = Setpoint frequency

9 = Error coder

10 = ... 11 reserved

12 = Bus IO Out Bits 0-7

13 = ... 16 reserved

17 = Value analog in 1, "Value of analog input 1"

SK2x0E: Analog input 1 (P400[-01]),

SK2x5E: AIN1 of the first I/O extension
SK xU4-IOE (P400 [-03]))

18 = Value analog in 2, "Value of analog input 2"

SK2x0E: Analog input 2 (P400[-02]),

SK2x5E: AIN2 of the first I/O extension
SK xU4-IOE (P400 [-04]))

19 = Freq.

master value, "Setpoint frequency

master value"

20 = Set freq after ramp master value,

"Setpoint frequency from ramp master value

21 = Act freq.wo.

slip master

"Actual frequency without slip master value"

22 = Speed encoder

23 = Actual with slip

(SW V1.3 and above)

"Actual frequency with slip"

24 = Master actual

(SW V1.3 and above)

"Actual frequency master value with slip"