PotentiometerBox SK TU4-POT-

The PotentiometerBox SK TU4-POT enables simple motor speed and direction control via a series SK 2x5E
frequency inverter. LEDs on the enable keys indicate the selected enable direction. In addition, with the
integrated mains unit, the 24V control voltage for the FI is produced from the mains voltage
(115V/230V/380V/500V). With this, a separate external 24V control voltage is not necessary.

Mains unit for 100-240V, SK TU4-POT-123-B

Mains unit for 380-500V, SK TU4-POT-140-B

+24V- output voltage

Button ON R / OFF / ON L

Setpoint potentiometer 0…100%

1 x impulse output (for setpoint)

Status LED = 24V, enable R, enable L

Max. permissible continuous current (Mains Unit): 420mA


The -SK TU4-

POT… is operated in combination with an SK TI4-TU-NET connection unit.

Details of the control connections can be found in the connection unit section (Section 3.5.1.2).

Connection plan, example:





SK 2x5E inverter series

Co

ntro

l terminal b

ar

44
40

.
.

21
22
23

.
.

L1 - L2/N - L3

115/230/400V




PotentiometerBox
SK TU4-POT-...
+ SK TI4-TU-NET

L1 - L2/N

115/230/400V

24V=

GND

R

L

0-100%

1/3~ 115/230/400V + PE

Control terminal bar

43 40 43 ... B1 B2 B3

Poten-

tiometer

0-10

0

L

R

DIP switch settings:

DIP3 = off, DIP4 = on, DIP5 = off

or

(With this, no further parameter settings are necessary!

See also Section 5.2.2.2)

recommended

parameter setting, DIP1-8 = off:

P400 [07] = 1 P420 [02] = 2

P420 [01] = 1 P420 [03] = 26

NOTE

Use of the SK TU4-POT on the SK 2x0E is not permissible!

A mains unit is integrated into the SK 2x0E inverter models, so that no external 24V DC is
required.