2 process controller parameter settings – NORD Drivesystems BU0200 User Manual

Page 284

Advertising
background image

9 Additional Information

BU 0200 GB-4411

Subject to technical alterations

283

9.2.2

Process controller parameter settings

(Example: Setpoint frequency: 50 Hz, control limits: +/- 25%)

P105 (Maximum frequency) [Hz]

:

 

 

 

%

%

.

.

100

415

P

Hz

q

Setpointfr

Hz

q

Setpointfr

Example:

%

100

%

25

50

50

Hz

Hz

62,5Hz

P400 [-01] (Funct. Analog input1)

:

"2“" (frequency addition)

P411 (Setpoint frequency) [Hz]

: Setpoint frequency with 10V at analog input 1


Example: 50 Hz

P412 (Process controller setpoint) : Central setting of compensating roller / factory setting 5V (adjust if
necessary)

P413 (P-controller) [%]

: factory setting 10% (adjust if necessary)

P414 (I-controller) [%/ms]

: recommended 100%/s

P415 (Limit +/-) [%]

: Control limit (see above)

Note:

Parameter P415 is used as a control limit after the PI controller.

Example: 25% of setpoint

P416 (Ramp time PI setpoint) [s]

: factory setting 2s (if necessary match to controller characteristics)

P420 [-01] (Funct. Digital input 1)

: "1"Enable right

P400 [-02] (Funct. Analog input 2) : "6"PI process controller actual value