116 DataSite Flow Configuration Utility (DS FloConfig)

Configure Serial Port Settings

Each 1758-FLO DataSite controller has one RS232/RS485 combo port
(COM1, default as RS232), and one RS232 port (COM2).

The default baud rate of each serial port is 9600 bps and the default station
number is 1.

Follow these steps to change the settings of the serial ports.

1.

In the FLO Communication dialog box, set up the parameters for the
serial ports.

This table shows the options and/or value range available for each
parameter.

Serial port parameters

Parameter

Parameter Options or Value Range

Station

1…247

Protocol

DS Workbench (for COM2 only), Modbus RTU,
Modbus ASCII, None

Mode

Master, Slave

Duplex

Full, Half

Baud

2400, 4800, 9600, 14400, 19200, 38400, 56000,
57600

Parity

Even, Odd, None

Data bit

7, 8

Stop bit

1, 2

Type

RS232, RS485

Timeout (in units of 10 ms)

1…1000

Delay (in units of 10 ms)

0…300