Enron Modbus Protocol for the 1758-FLO DataSite Controller 337

Hourly and Daily History

Enron Modbus hourly/daily archive registers are used to read the hourly and
daily logs on the 1758-FLO DataSite controller. The records are read one at a
time.

Each hourly and daily record has a fixed length with 64 float data bytes in the
following format as shown in the table.

Meter run 7 data variables

Register

Data Type

Description

3401…3500

Short integer

Meter run 7 data variables

Identical structure to meter run 0 data variables.

Offset by a value of 350.

5071…5080

Long integer

Meter run 7 data variables

Identical structure to meter run 0 data variables.

Offset by a value of 70.

7701…7800

Float

Meter run 7 data variables

Identical structure to meter run 0 data variables.

Offset by a value of 700.

Format of hourly and daily records

Field

Size

Type

Description

Date

4

FLOAT

Log date: MMDDYY.0

Time

4

FLOAT

Log time: HHMMSS.0

P_avg

4

FLOAT

Average pressure

T_avg

4

FLOAT

Average temperature

DP_avg

4

FLOAT

Average differential pressure or meter pulses

Gr

4

FLOAT

Relative density

Flow time

4

FLOAT

Run time yesterday

Volume_B

4

FLOAT

Total volume at base conditions

Volume_F

4

FLOAT

Total volume at flowing conditions

Volume_M

4

FLOAT

Total mass

Extension

4

FLOAT

Extension or uncorrected flow volume

Q Energy

4

FLOAT

Energy

VAR1

4

FLOAT

User defined variable