138 DataSite Flow Configuration Utility (DS FloConfig)

Cut-off Differential

When the differential pressure is lower than the value entered in the
Cut-off Differential box, the DataSite controller will consider any flow
as inexistent.

There will be a cutoff alarm in the Meter Run window, and the flow
rates become zero when this happens.

Tap Location

This is the location of the flange taps. It could be on the upstream or the
downstream of the orifice plate.

Orifice Plate Parameters for AGA3 Standard

Orifice Material and Tube Material

Specify the material of the orifice plate and pipe tube by selecting it
from the drop-down lists. These three materials are listed:

304 and 316 stainless steel

Carbon steel

Monel

Orifice Diameter

This is the inner diameter of the orifice plate measured at the reference
temperature specified in the Reference T box.