Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 327

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

Enron Modbus Protocol for the 1758-FLO DataSite Controller 327

General input configuration variables

Register

Description

Access

3053

Input unit type.
Bit 3: 0 = US, 1 = Metric

R/W

3054

Flow calculation type.
0 = AGA-3 (1992), 1 = AGA-7

R/W

3055

Compressibility calculation type
0 = Gas analysis, 1 = HR-GR-COR, 2 = GR-CO2-N2

R/W

3056

Static pressure tap location
0 = upstream, 1 = downstream

R/W

3057

Pressure type
0 = gauge, 1 = absolute

R/W

3058

Time duration for low flow pulse limit check (in seconds).
Range: 0…5 s (AGA-7 only)

R/W

3059

Calculation interval

R/W

Instantaneous input register address

Register

Description

Access

3060

Temperature input register Modbus address

R/W

3061

Static pressure input register Modbus address

R/W

3062

Differential pressure input register Modbus address

R/W

AGA-3 configuration variables

Register

Description

Access

3063

Orifice material
0 = stainless, 1 = monel, 2 = carbon steel

R/W

3064

Tube material
0 = stainless, 1 = monel, 2 = carbon steel

R/W

Instantaneous input register data type

Register

Description

Access

3065

DP register data type
0 = ushort, 1 = float

R/W

3066

P register data type
0 = ushort, 1 = float

R/W

3067

T register data type
0 = ushort, 1 = float

R/W