Publication 1758-UM002D-EN-P - October 2010

60 DataSite Configuration Settings Utility (DS Settings)

Unit register

+0 = unit

HART state register

+0 = state 0

+1 = state 1

Command

2

Purpose

Read primary variable current and percentage of span

Send register

Not used

Return register

+0, 1 = P. V. current mA (float point)

+2, 3 = P. V. percentage (float point) Purpose

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

3

Purpose

Read dynamic variables and primary variable current

Send register

Not used

Return register

+0, 1 = Primary Variable current (float point)

+2, 3 = Primary Variable value (float point)

+4, 5 = Secondary Variable value (float point)

+6, 7 = Tertiary Variable value (float point)

+8, 9 = Fourth Variable value (float point)

Unit register

+0 = Primary Variable unit code, 8-bit unsigned integer

+1 = Secondary Variable unit code, 8-bit unsigned integer

+2 = Tertiary Variable unit code, 8-bit unsigned integer

+3 = Fourth Variable Unit code, 8-bit unsigned integer

HART state register

+0 = state 0

+1 = state 1

Note

Not all equipment return primary, secondary, tertiary and fourth
variables. If the equipment does not support them, zero is written
into the value and units unit code for that variable.

Command

15

Purpose

Read Transmitter Variables

Send register

Not used

Return register

+0 = alarmselect code

+1 = transfer function code, 8-bit unsigned integer

+2 = P. V. range units code, 8-bit unsigned integer

+3, 4 = upper range value (float point)

+5, 6 = lower range value (float point)

+7, 8 = damping value (second) (float point)

+10 = private-label distributor code, 8-bit unsigned integer

Description of HART commands (Continued)