Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 62

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

62 DataSite Configuration Settings Utility (DS Settings)

Send register

+0, 1 = Actual fixed Primary Variable current level, units of
milliamperes (float point)

Return register

Not used

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

44

Purpose

Write Primary Variable Units

Send register

+0 = Primary Variable units code, 8-bit unsigned integer

Return register

Not used

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

48

Purpose

Read Additional Transmitter Status

Send register

Not used

Return register

+0, 2 = device specific status, 8-bit unsigned integer

+3 = Operational modes, 8-bit unsigned integer

+4, 5 = Analog outputs saturated, 24-bit unsigned integer

+6, 7 = Analog outputs fixed, 24-bit unsigned integer

+8, 13 = Device-specific status, 8-bit unsigned integer

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

54

Purpose

Read Transmitter Variable Information

Send register

+0 = Code for transmitter variable to be zeroed, 8-bit unsigned
integer

Return register

+0 = Return code for transmitter variable to be zeroed, 8-bit
unsigned integer

+1, 2 = Transmit variable sensor serial number, 24-bit unsigned
integer

+3 = Transmit variable limits units code,8-bit unsigned integer

+4, 5 = Transmit variable upper limit (float point)

+6, 7 = Transmit variable lower limit (float point)

+8, 9 = Transmit variable damping value (seconds) (float point)

+10, 11 = Transmit variable minumum span (float point)

Description of HART commands (Continued)