Command number 1: correct the system time – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 283

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

Extension Modbus Protocol for DataSite Controllers (1758-FLO) 283

Command Number 1: Correct the System Time

Use command number 1 to set up the system time of the 1758-FLO DataSite
controllers.

IMPORTANT

Enter a valid time, such as 2009-2-21 13:59:00.
The day of the week should correspond to the date.

Parameters for command number 1

Address

Data Type

Attribute

Description

49025

u_short

RW

1

49026

u_short

R

Return code

49027

u_short

W

Reserved

49028

u_int

W

Pass code for user

49030…49034

Reserved

49035

u_short

W

Year (0…99)

49036

u_short

W

Month (01…12)

49037

u_short

W

Day (01…31)

49038

u_short

W

Hour (00…23)

49039

u_short

W

Minute (00…59)

49040

u_short

W

Second (00…59)

49041

u_short

W

Week (01…07)

Event codes for command number 1

Event Name

Event Code

EVENT_SETDATE

5

EVENT_SETTIME

6

Advertising