Publication 1758-UM002D-EN-P - October 2010

256 DataSite DNP3 Configuration Utility (DS DNP3)

5.

If you want the host computer to check the RTC of the DataSite
controller periodically, select the Time Synchronization box. Then, in
the Interval box, specify how often you want the host computer to
check the RTC of the controller. The value range of the Interval
parameter is 0…999999999 and the default value is 1800000. Interval
parameter is 0 when you select the At Start Up Only check box.

6.

Enter the values for the DI, AI, and String events accordingly.

Download the Configuration file

For a new DNP3 configuration to take effect, the configuration file needs to
be downloaded to the DataSite controller after editing.

Follow this step to download the DNP3 configuration.

From the Control menu, choose Download.

You can also click the Download button

on the toolbar.

40

3

Short floating-point analog output state

50

0

Time and date

50

1

Time and date

51

1

Time and date CTO

80

1

Internal indications

110

String
length

Octet string object

111

String
length

Octet string event object

Event parameters

Parameter

Description

Range of Options or Values

Event mode

Event reporting mode

Last value: Only one event is retained
in the buffer for each point.
Queue: All events will be retained.

Event buffer
length

Maximum number of events
buffered by the controller

0…2000 for DI and AI events.
0…10 for String events.

Event scan time

Interval of the controller
scanning the events

0…99999

SDNP3 object library (Continued)

Object No.