Publication 1758-UM002D-EN-P - October 2010

Extension Modbus Protocol for DataSite Controllers (1758-FLO) 301

Command Number 18: Read the Calculation Input Parameter

Use command number 18 to read the parameter settings, excluding the gas
component parameter settings, for one meter run.

Return codes for command number 17

Return Code

Description

00

OK

01

Meter run is invalid

02

Disable/enable setting of meter run is invalid

03

Unit of measurement is invalid

04

Accumulate setting is invalid

05

Setting for the use of automatic component analysis instrument is
invalid

06

Calculation type is invalid

07

Algorithm selected for the calculation of the compressibility factor
is invalid

08

Pressure type is invalid

09

Tap location is invalid

10

Orifice material is invalid

11

Tube material is invalid

12

Relative density type is invalid

13

Interval for collecting the components from analysis instrument
automatically is invalid

100

Pass code is incorrect

Other

Invalid

Parameters for command number 18

Address

Data Type

Attribute

Description

49025

u_short

RW

18

49026

u_short

R

Return code

49027

u_short

W

Meter run (0…7)

49028

u_int

W

Pass code for user

49030…49034

Reserved

49035

u_short

R

Whether the meter run is enabled
0: Disable
1: Enable