Publication 1758-UM002D-EN-P - October 2010

DataSite Flow Configuration Utility (DS FloConfig) 187

Test the Communication

Follow these steps to obtain the communication settings of the DataSite
controller. This function can help you retrieve the communication parameter
settings if you forget or lose them.

1.

Set the controller into the Service mode.

2.

Select the Communication Test check box.

3.

Click Set.

All settings will be downloaded into the controller.

4.

Click Run followed by Close.

The controller goes into the Communication Test mode. The
communication parameters of COM2 are set to be test parameters.
This table lists the communication test parameters.

COM2 communication test parameters

Parameter Name

Parameter Value

Station

1

Protocol

Modbus RTU

Master/Slave State

Slave

Duplex

Full

Baud rate (bps)

57600

Parity

None

Data bits

8 bits

Stop bits

1 bit

Port type

RS232

Timeout (10 ms)

100

Delay time (10 ms)

0