Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 215

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

DataSite Flow Configuration Utility (DS FloConfig) 215

Unit register

+0 = Primary Variable unit code, 8-bit unsigned integer

+1 = Secondary Variable unit code, 8-bit unsigned integer

+2 = Tertiary Variable unit code, 8-bit unsigned integer

+3 = Fourth Variable Unit code, 8-bit unsigned integer

HART state register

+0 = state 0

+1 = state 1

Note

Not all equipment return primary, secondary, tertiary and fourth
variables. If the equipment does not support them, zero is written
into the value and units unit code for that variable.

Command

15

Purpose

Read Transmitter Variables

Send register

Not used

Return register

+0 = alarmselect code

+1 = transfer function code, 8-bit unsigned integer

+2 = P. V. range units code, 8-bit unsigned integer

+3, 4 = upper range value (float point)

+5, 6 = lower range value (float point)

+7, 8 = damping value (second) (float point)

+10 = private-label distributor code, 8-bit unsigned integer

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

33

Purpose

Read appointed transmitter variables

Send register

+0 = variable 0 code, 8-bit unsigned integer

+1 = variable 1 code, 8-bit unsigned integer

+2 = variable 2 code, 8-bit unsigned integer

+3 = variable 3 code, 8-bit unsigned integer

Return register

+0, 1 = Variable 0 value (float point)

+2, 3 = Variable 1 value (float point)

+4, 5 = Variable 2 value (float point)

+6, 7 = Variable 3 value (float point)

Unit register

+0 = Variable 0 unit code, 8-bit unsigned integer

+1 = Variable 1 unit code, 8-bit unsigned integer

+2 = Variable 2 unit code, 8-bit unsigned integer

+3 = Variable 4 unit code, 8-bit unsigned integer

Description of HART commands (Continued)