Command number 21: reset accumulation – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 308

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

308 Extension Modbus Protocol for DataSite Controllers (1758-FLO)

There is no event code for command number 20.

Command Number 21: Reset Accumulation

Use command number 21 to clear accumulation to zero for one meter run.

There is no event code for command number 21.

Return codes for command number 20

Return Code

Description

00

OK

01

Meter run is invalid

100

Pass code is incorrect

Other

Invalid

Parameters for command number 21

Address

Data Type

Attribute

Description

49025

u_short

RW

21

49026

u_short

R

Return code

49027

u_short

W

Meter run (0…7)

49028

u_int

W

Pass code for user

Return codes for command number 21

Return Code

Description

00

OK

01

Meter run is invalid

100

Pass code is incorrect

Other

Invalid