Configure tcp/ip settings – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 118

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

118 DataSite Flow Configuration Utility (DS FloConfig)

Configure TCP/IP Settings

Follow these steps to configure the Ethernet port.

1.

Under Ethernet in the FLO Communication dialog box, set up the
parameters of the Ethernet port.

This table shows the value range for each parameter.

2.

In the Communication Password box, enter the password you have
previously set in the PC Communication dialog box. See

Change the

Communication Password on page 120

.

3.

Click Download.

The new settings are applied to the DataSite controller.

TCP/IP port parameters

Parameter

Parameter Value Range

MAC

xx:xx:xx:xx:xx:xx

6 integers in hexadecimal format. For example, 00:00:BC:60:61:D0.
The MAC address is read-only.

IP

xxx.xxx.xxx.xxx

4 octets with each octet ranging from 0…255.
The default value is 192.168.100.75.

Mask

xxx.xxx.xxx.xxx

4 octets with each octet ranging from 0…255.

Gateway

xxx.xxx.xxx.xxx

4 octets with each octet ranging from 0…255.

Port

502

The port number of DS Settings TCP/IP port is defined as 502
when the PC is connected to the DataSite controller.

Station

1

The default value is 1.