36 DataSite Configuration Settings Utility (DS Settings)

Block Type

The block type indicates the category of scan block data.

Scan blocks are configured in sequence, and every block has a corresponding
number. The maximum number of block numbers is 128.

When the type of a block is Empty Block, its subsequent block configuration
is invalid.

Module Addr

For 1758-RTU controller, this means the Modbus slave station number of the
serial communication equipment connected with COM1 or COM2.

The range of the Modbus slave station number is 1…247.

Signal Type

The signal type indicates the category of register read/write signal, and its
contents.

Scan block types and their descriptions

Name

Function

US1 block

1758-RTU controller Read-write data of the serial
equipment connected with the serial port COM1.

US2 block

1758-RTU controller Read-write data of the serial
equipment connected with the serial port COM2.

Empty block

Scan block configuration end flag

Signal types and functions

Signal Type

Function

Modbus Command

Read_Coil register

Read 00001…04096 register

1

Read_State register

Read 10001…14096 register

2

Read_Hold register

Read 40001…49999 register

3

Read_Input register

Read 30001…31024 register

4

Write_1Coil register

Write 00001…04096 register

5

Write_1Hold register

Write 40001…49999 register

6

Write_nCoil register

Write 00001…04096 register

15

Write_nHold register

Write 40001…49999 register

16