Publication 1758-UM002D-EN-P - October 2010

70 DataSite Configuration Settings Utility (DS Settings)

5.

In the Scan Time box, enter the number of units and select the time unit
to specify the time cycle of scanning HART equipment data.
For example, if you enter "1" for the number of units, and select
"(500 ms)" for the time unit, the scan time will be 1 x 500 ms = 500 ms.
This means that the current HART scan block will be executed every
500 ms.

6.

In the Send Register box, define the register for storing command data.

7.

In the Return Register box, define the register for storing command
response data.

8.

In the Unit Register box, define the register for storing the unit of
HART equipment data returned.

9.

In the HART State Addr box, define the register for storing the HART
equipment state returned.

10.

Click OK.

The Edit dialog box is closed and the settings are saved to the new
block.

35

Write Primary Variable Range Values

Only Use in HART TRIG block

38

Reset Configuration Changed Flag

40

Enter/Exit Fixed Primary Variable Current Mode

Only Use in HART TRIG block

44

Write Primary Variable Units

Only Use in HART TRIG block

48

Read additional Transmitter Status

54

Read Transmitter Variable Information

59

Write Number Of Response Preambles

Only Use in HART TRIG block

Effective values of HART commands (Continued)

Effective Value

HART Commands

Effective Value

IMPORTANT

Command 0 must be configured for each HART device in
order for the other commands to work.

TIP

The register range is 40003…49999 for 1758-RTU
controllers, and 40003…47999 for 1758-FLO controllers.

See

Description of HART commands on page 58

for more

information on the Send, Return, Unit, and HART State
Addr registers.