1 of, Valid range of gas characteristics for – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 148

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

148 DataSite Flow Configuration Utility (DS FloConfig)

6.

To save this configuration, click Save.
The Save button is located to the right of the Field Signal parameters in
the Meter Run window.

7.

Click Download to apply the settings to the DataSite controller.

Valid Range of Gas Characteristics for AGA8 Methods

This table identifies the ranges of gas characteristics for which the AGA8
report can be used.

IMPORTANT

The mole percentage of each component, heating value
and relative density should not exceed the range which is
listed in table 1 of

Valid Range of Gas Characteristics for

AGA8 Methods on page 148

.

Quantity

Normal Range

Expanded Range

Relative density

0.56…0.87

0.07…1.52

Gross heating value

(1)

(1)

Reference conditions are as follows: Combustion at 60 ºF, 14.73 psia; density at 60 ºF, 14.73 psia.

477…1150 Btu/scf

0…1800 Btu/scf

Methane mole percent

45.0…100.0

0…100.0

Nitrogen mole percent

0.0…50.0

0…100.0

Carbon dioxide mole percent

0.0…30.0

0…100.0

Ethane mole percent

0.0…10.0

0…100.0

Propane mole percent

0.0…4.0

0…12.0

Butane mole percent

0.0…1.0

0…6.0

Pentane mole percent

0.0…0.3

0…4.0

Hexane mole percent

0.0…0.2

0…Dew point

Helium mole percent

0.0…0.2

0…3.0

Hydrogen mole percent

0

(2)

(2)

The normal range is considered to be zero for these compounds.

0…100.0

Carbon monoxide mole percent

0

(2)

0…3.0

Argon mole percent

0

(2)

0…1.0

Oxygen mole percent

0

(2)

0…21.0

Water mole percent

0.0…0.05

0…Dew point

Hydrogen sulfide mole percent

0.0…0.02

0…100.0

Advertising