Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 214

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

214 DataSite Flow Configuration Utility (DS FloConfig)

Return register

+0 = manufacturer ID code, 8-bit unsigned integer

+1 = manufacturer equipment type code, 8-bit unsigned integer

+2 = forerunner character number, 8-bit unsigned integer

+3 = global command revision level, 8-bit unsigned integer

+4 = transmitter revision level, 8-bit unsigned integer

+5 = software revision level, 8-bit unsigned integer

+6 = hardware revision level, 8-bit unsigned integer

+7 = equipment function flags, 8-bit unsigned integer

+8, 9 = Device Identification Number (double), 24-bit unsigned
integer

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

1

Purpose

Read primary variable (P. V.)

Send register

Not used

Return register

+0, 1 = P. V. (float point)

Unit register

+0 = unit

HART state register

+0 = state 0

+1 = state 1

Command

2

Purpose

Read primary variable current and percentage of span

Send register

Not used

Return register

+0, 1 = P. V. current mA (float point)

+2, 3 = P. V. percentage (float point) Purpose

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

3

Purpose

Read dynamic variables and primary variable current

Send register

Not used

Return register

+0, 1 = Primary Variable current (float point)

+2, 3 = Primary Variable value (float point)

+4, 5 = Secondary Variable value (float point)

+6, 7 = Tertiary Variable value (float point)

+8, 9 = Fourth Variable value (float point)

Description of HART commands (Continued)