Publication 1758-UM002D-EN-P - October 2010

Extension Modbus Protocol for DataSite Controllers (1758-FLO) 287

Command Number 6: Read the Disable/Enable Flow Calculation
Setting

Use command number 6 to read the disable/enable setting of the flow
calculation for a meter run.

There is no event code for command number 6.

Event codes for command number 5

Event Name

Event Code

EVENT_RUN_ENABLE

11

EVENT_RUN_DISABLE

12

Return codes for command number 5

Return Code

Description

00

OK

01

Meter run is invalid

02

Input value is invalid

100

Pass code is incorrect

Other

Invalid

Parameters for command number 6

Address

Data Type

Attribute

Description

49025

u_short

RW

6

49026

u_short

R

Return code

49027

u_short

W

Meter run (0…7)

49028

u_int

W

Pass code for user

49030…49034

Reserved

49035

u_short

R

0: Disable
1: Enable

Return codes for command number 6

Return Code

Description

00

OK

01

Meter run is invalid

100

Pass code is wrong

Other

Invalid