Publication 1758-UM002D-EN-P - October 2010

Extension Modbus Protocol for DataSite Controllers (1758-FLO) 289

There is no event code for command number 8.

Command Number 9: Set Up the Input Signal Test

Use command number 9 to set up the input signal test for one meter run.

49035

u_short

R

Contract hour (0…23)

49036

u_short

R

Contract minute (0…59)

49037

u_short

Reserved

Return codes for command number 8

Return Code

Description

00

OK

100

Pass code is wrong

Other

Invalid

Parameters for command number 9

Address

Data Type

Attribute

Description

49025

u_short

RW

9

49026

u_short

R

Return code

49027

u_short

W

Meter run (0…7)

49028

u_int

W

Pass code for user

49030…49034

Reserved

49035

u_short

W

Whether differential pressure or
pulse tested.
0: No test
1: Test

49036

u_short

W

Whether static pressure tested.
0: No test
1: Test

49037

u_short

W

Whether temperature tested.
0: No test
1: Test

49038

float

W

Differential pressure or pulse test
value

49040

float

W

Static pressure test value

49042

float

W

Temperature test value

Parameters for command number 8 (Continued)

Address

Data Type

Attribute

Description