Publication 1758-UM002D-EN-P - October 2010

DataSite Flow Configuration Utility (DS FloConfig) 153

5.

To save the configuration to a file buffer on the PC, click Save.

The message, “Save successful” appears.

6.

Click OK to close the message box.

7.

Click Download.

The configuration is downloaded into the controller. At the same time,
the message, “Download successful” appears.

8.

Click OK to close the message box.

Variables for Daily Historical Records

This table shows the variables you can log in the daily historical records.
The details of some of the variables can be found in

Display the Flow Results

of a Meter Run on page 124

.

For more information, see

Display the Flow Results of a Meter Run on page

124

.

TIP

The total number of daily records is 35.

Variable

Description

av_P

Daily average value of pressure.

av_T

Daily average value of temperature.

av_DP/PI

Daily average value of differential pressure (AGA3), in H2O at 60 °F,
or pulse input count per second (AGA7), in counts/s.

Density

Average real relative density for the day.

Flow time

Flow time for the day.

qvn

Volume flow quantity of the last contract day in base conditions.

qvf

Volume flow quantity of the last contract day in flowing conditions.

qm

Mass flow quantity of the last contract day.

EXT/Uncorrected
volume

Daily average of Flow Extension or Uncorrected Flow Volume.

Energy

Reserved. The value is zero.

User var1

An instantaneous value of the last contract day. This variable is
user-configurable.

User var2

User var3

User var4