Command number 25: read new alarm logs – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 314

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

314 Extension Modbus Protocol for DataSite Controllers (1758-FLO)

There is no event code for command number 24.

Command Number 25: Read New Alarm Logs

Use command number 25 to read new alarm logs. The value in register 49030
indicates how many new alarm records have been loaded with this reading.
The maximum number is 15. Each new alarm record consists of 12 registers
and has the same format as an alarm.

49083…49094

See above

See above

Alarm 5

49095…49106

See above

See above

Alarm 6

49107…49118

See above

See above

Alarm 7

49119…49130

See above

See above

Alarm 8

49131…49142

See above

See above

Alarm 9

49143…49154

See above

See above

Alarm 10

49155…49166

See above

See above

Alarm 11

49167…49178

See above

See above

Alarm 12

49179…49190

See above

See above

Alarm 13

49191…49202

See above

See above

Alarm 14

49203…49214

See above

See above

Alarm 15

Return codes for command number 24

Return Code

Description

00

OK

01

Meter run is invalid

02

Number of records you want to get is invalid

100

Pass code is incorrect

Other

Invalid

Parameters for command number 25

Address

Data Type

Attribute

Description

49025

u_short

RW

25

49026

u_short

R

Return code
0: OK

49027

u_short

W

Reserved

49028

u_int

W

Pass code for user

49030

u_short

R

Number of read records

Registers for alarms 2…15 (Continued)

Address

Data Type

Attribute

Description