Publication 1758-UM002D-EN-P - October 2010

DataSite Flow Configuration Utility (DS FloConfig) 137

Configure AGA3 Process Parameters

If you choose the AGA3 gas flow calculation standard, you need to configure
these parameters:

Instrument parameters

Orifice Plate parameters

Instrument Parameters for AGA3 Standard

Base Pressure and Base Temperature

This is the pressure and temperature under base conditions.

Pressure Type

This is the static pressure type tested by pressure meter. The pressure
type could be an absolute static pressure or gauge static pressure.

If it is the absolute static pressure, then entering the atmospheric
pressure is not required.

Absolute static pressure = Gauge static pressure + Atmospheric
pressure

TIP

For any changes to parameter settings to be applied to the
DataSite controller, you need to click Download.

IMPORTANT

Before downloading any changes to the DataSite controller,
it is recommended that you perform an upload. This helps
prevent modifying information that you did not intend to
change.